KOHLER.SDMO KR230U 发电机组 柴油机零件 226千瓦
柴油发电机/ KR230U
KOHLER-SDMO电力产品系列的标准发电机组可提供7.5至4,200 kVA的所有电力需求。它们专为工业用户设计,涵盖广泛的应用领域,提供广泛的选项和改造,以完全满足所有配置的要求。
通过安全的工程工具门户构建您的能源解决方案。使用尺寸调整程序功能,通过Spec Editor生成技术规格,并从产品目录中查看有关KOHLER-SDMO工业发电机组的详细信息。
主要评级: |  | 205千瓦(256千伏安) |
|
待机评级: |  | 226千瓦(282千伏安) |
|
赫兹: |  | 60赫兹 |
|
交流发电机类型: |  | 4极,旋转场 |
|
引擎制造商: |  | 约翰迪尔 |
|
发动机型号: |  | 6090HFS85 |
|
气缸布置: |  | 6内联 |
|
额定转速下的最大功率: |  | 258.4千瓦(346.5 BHP) |
|
优质燃油消耗量 |  |
|
100%负载: |  | 58.8 Lph(15.5 gph) |
75%负载: |  | 44.7 Lph(11.8 gph) |
50%负载: |  | 32.4 Lph(8.56 gph) |
|
KR230U
Engine type Alternator type Canopy typePerformance class
6090HFS85 AT01512T M3227G3
GENERAL CHARACTERISTICS
Frequency (Hz)
60
Voltage (V)
480/277
Max power ESP (kVA)
282
Max power ESP (kWe)
226
Max power PRP (kVA)
256
Max power PRP (kWe)
205
Intensity (A)
339
Standard control panel
APM303
Optional control panel
DEC4000
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual
operating hours in variable load applications, in accordance with
ISO 8528-1. ESP : The standby power rating is applicable for
supplying emergency power in variable load applications in
accordance with ISO 8528-1. Overload is not allowed.
TERM OF USE
According to the standard, the nominal power assigned by the genset
is given for 25°C Air Intlet Temperature, of a barometric pressure of
100 kPA (100 m A.S.L), and 30 % relative humidity. For particular
conditions in your installation, refer to the derating table.
SMALL AUTONOMY DIMENSIONS
4332
1361
2431
4090
1083
N/A
Length (mm).
Width (mm).
Height (mm).
Dry weight (kg).
Tank capacity (L).
Autonomy @ 75% of load (h)
Autonomy @ 50% of load (h) N/A
SOUND LEVELS
0 (0.7)
N/A
Acoustic pressure level @1m in dB(A)
Acoustic pressure level @7m in dB(A)
ASSOCIATED UNCERTAINTY
For the generating sets used indoor, where the acoustic pressure
levels depends on the installation conditions, it is not possible to
specify the ambient noise level in the exploitation and maintenance
instructions . You will also find in our exploitation and maintenance
instructions a warning concerning the air noise dangers and the need
to implement appropriated preventive measures.
DESCRIPTIVE
Connection terminal box rental type
Containment fuel tank and large autonomy Forks and frame protection pads
Battery isolating switch
Heavy duty air filter with interchangeable cartridge
Access door to the radiator
KR230U
ENGINE SPECIFICATIONS
JOHN DEERE
6090HFS85
Turbo
L
6
8.98
118.4 x 136
1800
8.16
258.4
+/- 0.5%
17.5
GENERAL ENGINE DATA
Engine model
Engine type
Air inlet
Cylinders arrangement
Number of cylinders
Displacement (L)
Charge Air coolant
Bore (mm) x Stroke (mm)
Compression ratio
Speed (RPM)
Pistons speed (m/s)
Maximum stand-by power at rated
RPM (kW)
Frequency regulation, steady state (%)
BMEP (bar)
Governor type Electronic
COOLING SYSTEM
Radiator & Engine capacity (L) N/A
Max water temperature (°C) 110
Outlet water temperature (°C) N/A
Fan power (kW) N/A
Fan air N/A flow w/o restriction (m3/s)
Available restriction on air flow (mm
H2O)
Type of coolant
N/A
Glycol-Ethylene
Thermostat modulating range HT (°C) 85-95
N/A
N/A
N/A
EMISSIONS
Emission PM (g/kWh)
Emission CO (g/kWh)
Emission HC+NOx (g/kWh)
Emission HC (g/kWh) N/A
477
838
EXHAUST
Exhaust gas temperature @ ESP 60Hz (°C)
Exhaust gas flow @ ESP 60Hz (L/s)
Max. exhaust back pressure (mm H2O) 765
56.9
58.8
44.7
32.4
FUEL
Consumption @ 110% load (L/h)
Consumption @ 100% load (L/h)
Consumption @ 75% load (L/h)
Consumption @ 50% load (L/h)
Maximum fuel pump flow (L/h) N/A
31
1.9
2.4
N/A
OIL
Oil capacity (L)
Min. oil pressure (bar)
Max. oil pressure (bar)
Oil consumption 100% load (L/h)
Oil sump capacity (L) N/A
177
26
HEAT BALANCE
Heat rejection to exhaust (kW)
Radiated heat to ambient (kW)
Heat rejection to coolant (kW) 86.1
637
AIR INTAKE
Max. intake restriction (mm H2O)
Intake air flow (L/s) 352
16 : 1
Air/Water DC
KR230U
ALTERNATOR SPECIFICATIONS
GENERAL DATA
Alternator type AT01512T
Number of Phase Three phase
Power factor (Cos Phi) 0.8
Altitude (m) 0 to 1000
Overspeed (rpm) 2250
4
Yes
Number of pole
Capacity for maintaining short circuit at
3 ln for 10 s
Insulation class H
T° class (H/125°), continuous 40°C H / 125°K
T° class, standby 27°C H / 163°K
AVR Regulation Yes
Total Harmonic Distortion in no-load <2.5
DHT (%)
Total Harmonic Distortion, on load DHT
(%) <2.5
Wave form : NEMA=TIF <50
Wave form : CEI=FHT <2
Number of bearing 1
Coupling Direct
0.5
500
Voltage regulation at established rating
(+/- %)
Recovery time (Delta U = 20%
transient) (ms)
Protection class
Technology
IP 23
Without collar or
brush
OTHER DATA
Continuous Nominal Rating 40°C (kVA) 300
Standby Rating 337 27°C (kVA)
Efficiencies 100% of load (%) 92.8
Air flow (m3/s) 0.51
Short circuit ratio (Kcc) 0.413
Direct axis synchro reactance unsaturated (Xd) (%) 327
Quadrature-axis synchro reactance unsaturated (Xq)
(%)
Open circuit time constant (T'do) (ms) 2105
15.5
100
9.3
10
11.5
Direct axis transient reactance saturated (X'd) (%)
Short circuit transient time constant (T'd) (ms)
Direct axis subtransient reactance saturated (X''d) (%)
Subtransient time constant (T"d) (ms)
Quadrature-axis subtransient reactance saturated
(X"q) (%)
Subtransient time constant (T"q) (ms) 10
Zero sequence reactance unsaturated (Xo) (%) 0.6
Negative sequence reactance saturated (X2) (%) 10.42
Armature time constant (Ta) (ms) 15
1.03
3.9
52.2
599.38
14
5537.97
No load excitation current (io) (A)
Full load excitation current (ic) (A)
Full load excitation voltage (uc) (V)
Engine start (Delta U = 20% perm. or 50% trans.)
(kVA)
Transient dip (4/4 load) - PF : 0.8 AR (%)
No load losses (W)
Heat rejection (W)
Unbalanced load acceptance ratio (%)
18597.4
100
166
KR230U
CONTROL PANEL
DEC4000, ergonomic and user-friendly APM303, comprehensive and simple The APM303 is a versatile unit which can be operated in manual or automatic mode. It offers the following features:
Measurements:
phase-to-neutral and phase-to-phase voltages, fuel level
(In option : active power currents, effective power, power factors, Kw/h energy meter, oil pressure and coolant
temperature levels)
Supervision:
Modbus RTU communication on RS485
Reports:
(In option : 2 configurable reports)
Safety features:
Overspeed, oil pressure,coolant temperatures, minimum and maximum voltage, minimum and maximum frequency (Maximum active power P<66kVA)
Traceability:
Stack of 12 stored events
For further information, please refer to the data sheet for the
APM303.
The highly versatile DEC4000 control unit is complex yet
accessible, thanks to the particular attention paid to
optimising its ergonomics and ease of use. With its large
display screen, buttons and scroll wheel, it places the
accent on simplicity and communication.
The DEC4000 offers the following functions:
Electrical measurements: voltmeter, frequency meter,
ammeter.
Engine parameters: working hours counter, oil pressure, coolant temperature, fuel level, engine speed, battery
voltage.
Alarms and faults: oil pressure, coolant temperature, failure to start, overspeed, alternator min./max., battery voltage
min./max., emergency stop, fuel level.
Ergonomics: wheel for navigating around the various
menus.
Communication: remote control and operation software,
USB connections, PC connection.